2022 Title 24 Part 6 Prescriptive Requirements for Additions
An ADDITION is any change to a building that increases conditioned floor area and conditioned volume. Addition is also any change that increases the floor area and volume of an unconditioned building of an occupancy group or type regulated by Part 6. Addition is also any change that increases the illuminated area of an outdoor lighting application regulated by Part 6.
An option to meet the Title 24 Part 6 Energy Code is to use a "Prescriptive Path of Compliance." A Prescriptive Path of Compliance, follows a list of requirements without any deviation from the requirement. For example, if under the Prescriptive Path of Compliance the conditioned area of the home allows for 200 ft² of fenestration (1000 ft² Home × 20% = 200 ft² of fenestration allowed), then no more that 200 ft² of fenestration may be installed in the conditioned building. Another example is that if the Prescriptive Path of Compliance dictates that wall insulation is to be R-21 + an R-5 on the exterior or interior of the wall, then the walls must have R-21 between the studs and R-5 on the outside of the walls under the siding or on the inside of the walls.
Below is a list of Prescriptive requirements for Additions from the 2022 Single Family Residential Compliance Manual.
9.4 Prescriptive Approach and Mandatory Requirements
The prescriptive requirements apply to additions in the same way they apply to new buildings and must be documented on the CF1R-ADD-01 or CF1R-NCB-01 Form.
Except as noted, all applicable prescriptive requirements for additions must be met when using the prescriptive approach. Otherwise, the building must comply using the performance approach.
For prescriptive additions, a certificate of compliance (CF1R-ADD-01 or CF1R-NCB-01) form must be completed and submitted for permit. If any mandatory or prescriptive features require HERS verification or testing or both, the certificate of compliance for the project must be completed and registered online with a HERS Provider before submittal to the enforcement agency. Refer to Section 2.2.2 and Section 2.5.
9.4.1 Prescriptive Additions
There are three prescriptive paths available for additions based on the total conditioned floor area (CFA) of the addition. The total CFA of the addition may include floor areas representing several physically separate additions to the building under the same permit. Table 9-2 through Table 9-6 summarize the key prescriptive envelope requirements for the three prescriptive addition options in §150.2(a)1.
The prescriptive requirements for additions are listed in §150.2(a)1. Unless noted below, the newly constructed building prescriptive requirements contained in §150.1(c) also apply.
-
Additions ≤400 ft²
- Total glazing area up to 75 ft² or 30 percent of the conditioned floor area, whichever is greater.
- Total glazing area maximum for west-facing glazing is 60 ft² or 5 percent in Climate Zones 2, 4, and 6-15.
- QII does not apply.
- Rafter roof insulation of R-22.
- Ceiling insulation of R-38 in Climate Zones 1,2,4 and 8-16, or R-30 in Climate Zones 3 and 5-7.
- Radiant barrier in Climate Zones 2-15.
- Extensions of existing wood-framed walls (Figure 9-1) may retain the dimensions of the existing walls and require the following cavity insulation:
- In 2x4 wood-frame walls, insulation shall be R-15.
- In 2x6 or greater wood-frame walls, insulation shall be R-21.
- Existing wood-framed walls where existing exterior siding (or cladding) will not be removed, do not need continuous insulation, and require only cavity insulation:
- In 2x4 wood-framed walls, insulation shall be R-15.
- In 2x6 or greater wood-framed walls, insulation shall be R-21.
-
Additions >400 ft² and ≤700 ft²
- Total glazing area up to 120 ft² or 25 percent of the conditioned floor area.
- Total glazing area maximum for west-facing glazing is 60 ft² or 5 percent in Climate Zones 2, 4, and 6-15.
- QII does not apply.
- Rafter roof insulation of R-22.
- Ceiling insulation of R-38 in Climate Zones 1,2,4, and 8-16 or R-30 in Climate Zones 3 and 5-7.
- Radiant barrier in Climate Zones 2-15.
- Extensions of existing wood-framed walls may retain the dimensions of the existing walls and require the following cavity insulation:
- In 2x4 wood-framed walls, insulation shall be R-15.
- In 2x6 or greater wood-framed walls, insulation shall be R-21.
- Existing wood-framed walls, where existing exterior siding (or cladding) will not be removed, do not need continuous insulation, and require only cavity insulation:
- In 2x4 wood-framed walls, insulation shall be R-15.
- In 2x6 or greater wood-framed walls, insulation shall be R-21.
-
Additions >700 ft²
- Total glazing area up to 175 ft² or 20 percent of the conditioned floor area, whichever is greater.
- Total glazing area maximum for west-facing glazing is 70 ft² or 5 percent in Climate Zones 2, 4, and 6-15.
- Extensions of existing wood-framed walls may retain the dimensions of the existing walls and require the following cavity insulation:
- In 2x4 wood-framed walls, insulation shall be R-15.
- In 2x6 or greater wood-framed walls, insulation shall be R-21.
- Existing wood-framed walls, where existing exterior siding (or cladding) will not be removed, do not need continuous insulation, and require only cavity insulation:
- In 2x4 wood-framed walls, insulation shall be R-15.
- In 2x6 or greater wood-framed walls, insulation shall be R-21.
- QII applies to the addition.
- When an addition greater than 700 ft² is an existing unconditioned space converted to conditioned space, the QII requirements do not include:
- Window and door header insulation.
- Air sealing if the existing air barrier is not removed or replaced.